HF2721

Fire life safety damper testing established relating to state fire code.
Legislative Session 94 (2025-2026)

Related bill: SF2717

Bill text

Introduction

ReadChanges
PDF
(underlined = new law, struck through = current law the bill removes)
1.1A bill for an act
1.2relating to the State Fire Code; establishing fire life safety damper testing;
1.3authorizing rulemaking; proposing coding for new law in Minnesota Statutes,
1.4chapter 299F.
1.5BE IT ENACTED BY THE LEGISLATURE OF THE STATE OF MINNESOTA:
1.6Section 1. new text begin [299F.49] DEFINITIONS. new text end
1.7 new text begin Subdivision 1. Scope. As used in sections 299F.49 and 299F.491, the terms defined in new text end
1.8 new text begin this section have the meanings given. new text end
1.9 new text begin Subd. 2. Approved skill training program or program. "Approved skill training new text end
1.10 new text begin program" or "program" means an apprenticeship program that is registered under chapter new text end
1.11 new text begin 178 or Code of Federal Regulations, title 29, part 29. new text end
1.12 new text begin Subd. 3. Building. "Building" means a building equipped with fire life safety dampers, new text end
1.13 new text begin a smoke control system, or an HVAC duct system that contains fire life safety dampers or new text end
1.14 new text begin is part of a smoke control system. Building does not include single family residential new text end
1.15 new text begin buildings or multifamily buildings with four or fewer units. new text end
1.16 new text begin Subd. 4. Combination fire smoke damper. "Combination fire smoke damper" means new text end
1.17 new text begin a device that meets both the fire damper and smoke damper requirements. new text end
1.18 new text begin Subd. 5. Dedicated smoke control system. "Dedicated smoke control system" means new text end
1.19 new text begin a smoke control system and components that are installed for the sole purpose of providing new text end
1.20 new text begin smoke control and that upon activation of the systems operate specifically to perform the new text end
1.21 new text begin smoke control function. new text end
2.1 new text begin Subd. 6. Fire damper. "Fire damper" means a device installed in an air distribution new text end
2.2 new text begin system that is designed to close automatically upon detection of heat, to interrupt migratory new text end
2.3 new text begin airflow and to restrict the passage of flame. Fire damper includes devices installed in air new text end
2.4 new text begin conditioning systems to close automatically upon detection of heat, to interrupt migratory new text end
2.5 new text begin airflow, and to restrict the passage of flames. A fire damper also includes a combination new text end
2.6 new text begin fire smoke damper. new text end
2.7 new text begin Subd. 7. Fire life safety dampers. "Fire life safety dampers" means all fire dampers, new text end
2.8 new text begin smoke dampers, and combination fire and smoke dampers. new text end
2.9 new text begin Subd. 8. Fire life safety damper testing. "Fire life safety damper testing" means testing new text end
2.10 new text begin and inspection activities, including all physical, visual, and operational tests necessary to new text end
2.11 new text begin ensure the complete opening, closing, and the proper functioning of fire life safety dampers new text end
2.12 new text begin as required by the IFC, NFPA 80, NFPA 101, NFPA 105, and applicable engineering new text end
2.13 new text begin specifications of these systems. new text end
2.14 new text begin Subd. 9. HVAC. "HVAC" means heating, ventilation, and air conditioning. new text end
2.15 new text begin Subd. 10. ICB. "ICB" means the International Certification Board. new text end
2.16 new text begin Subd. 11. IFC. "IFC" means the International Fire Code. new text end
2.17 new text begin Subd. 12. Independent contractor. "Independent contractor" means a company that is new text end
2.18 new text begin not owned or managed by the building owner, or an immediate family member of the new text end
2.19 new text begin building owner, of the building being inspected and includes any subsidiary companies of new text end
2.20 new text begin the independent contractor. new text end
2.21 new text begin Subd. 13. ISO/IEC 17024. "ISO/IEC 17024" means the International Organization for new text end
2.22 new text begin Standardization/International Electrotechnical Commission 17024 international standard new text end
2.23 new text begin for Conformity Assessment - General Requirements for Bodies Operating Certification of new text end
2.24 new text begin Persons. new text end
2.25 new text begin Subd. 14. NFPA. "NFPA" means the National Fire Protection Association. new text end
2.26 new text begin Subd. 15. NFPA 80. "NFPA 80" means the current adopted version of the Standard for new text end
2.27 new text begin Fire Doors and Other Opening Protectives. new text end
2.28 new text begin Subd. 16. NFPA 92. "NFPA 92" means the current version of the Standard for Smoke new text end
2.29 new text begin Control Systems. new text end
2.30 new text begin Subd. 17. NFPA 101. "NFPA 101" means the current adopted version of the Standard new text end
2.31 new text begin for Life Safety Code. new text end
3.1 new text begin Subd. 18. NFPA 105. "NFPA 105" means the current adopted version of the Standard new text end
3.2 new text begin for Smoke Door Assemblies and Other Opening Protectives. new text end
3.3 new text begin Subd. 19. Nondedicated smoke control system. "Nondedicated smoke control system" new text end
3.4 new text begin means a smoke control system that shares components with some other system, such as the new text end
3.5 new text begin building HVAC system, that changes its mode of operation to achieve the smoke-control new text end
3.6 new text begin objective. new text end
3.7 new text begin Subd. 20. Qualified fire smoke damper inspector. "Qualified fire smoke damper new text end
3.8 new text begin inspector" means: new text end
3.9 new text begin (1) an authorized state or local fire department personnel; new text end
3.10 new text begin (2) the holder of a valid license delineated in section 326B.31, subdivision 2, 8, 9, 25, new text end
3.11 new text begin or 30; or new text end
3.12 new text begin (3) a technician certified by the ICB as a fire smoke damper technician or through an new text end
3.13 new text begin equivalent certification program accredited under the ISO/IEC 17024 personnel certification. new text end
3.14 new text begin The technician must be employed by an independent contractor that provides fire life safety new text end
3.15 new text begin damper inspection services and shall: new text end
3.16 new text begin (i) maintain current workers' compensation insurance coverage; new text end
3.17 new text begin (ii) hold an ICB Fire and smoke damper contractor certification, or equivalent new text end
3.18 new text begin certification, from an organization that has been accredited under the ISO/IEC 17024 new text end
3.19 new text begin Personnel Certification standard in fire life safety damper inspections; and new text end
3.20 new text begin (iii) participate in an approved skill training program. new text end
3.21 new text begin Subd. 21. Qualified smoke control system inspector. "Qualified smoke control system new text end
3.22 new text begin inspector" means: new text end
3.23 new text begin (1) an authorized state or local fire department personnel; new text end
3.24 new text begin (2) the holder of a valid license delineated in section 326B.31, subdivision 2, 8, 9, 25, new text end
3.25 new text begin or 30; or new text end
3.26 new text begin (3) a technician certified by ICB as a smoke control systems technician or through an new text end
3.27 new text begin equivalent certification program accredited under the ISO/IEC 17024 personnel certification. new text end
3.28 new text begin A smoke control systems technician shall also be a TABB technician certified by the new text end
3.29 new text begin Associated Air Balance Council, the National Environmental Balancing Bureau, or the new text end
3.30 new text begin Testing, Adjusting and Balancing Bureau. The technicians must be employed by an new text end
3.31 new text begin independent contractor that provides fire life safety damper testing services. The independent new text end
3.32 new text begin contractor must: new text end
4.1 new text begin (i) maintain current workers' compensation insurance coverage; new text end
4.2 new text begin (ii) hold an ICB smoke control system contractor certification or equivalent certification new text end
4.3 new text begin from an organization that has been accredited under the ISO/IEC 17024 Personnel new text end
4.4 new text begin Certification standard in smoke control systems inspections; and new text end
4.5 new text begin (iii) participate in an approved skill training program. new text end
4.6 new text begin Subd. 22. Smoke control system. "Smoke control system" means an engineered system new text end
4.7 new text begin that includes all methods that can be used singly or in combination to modify smoke new text end
4.8 new text begin movement, including engineered systems that use mechanical fans to produce pressure new text end
4.9 new text begin differences across smoke barriers to inhibit smoke movement. new text end
4.10 new text begin Subd. 23. Smoke damper. "Smoke damper" means a device within an air distribution new text end
4.11 new text begin system to control the movement of smoke. Smoke damper includes devices installed in air new text end
4.12 new text begin conditioning systems to control the movement of smoke. A smoke damper also includes a new text end
4.13 new text begin combination fire smoke damper. new text end
4.14 new text begin Subd. 24. Subsidiary. "Subsidiary" means any corporation or other organization, whether new text end
4.15 new text begin incorporated or unincorporated, in which the company owns, directly or indirectly, any new text end
4.16 new text begin equity or other ownership interest. new text end
4.17Sec. 2. new text begin [299F.491] FIRE LIFE SAFETY DAMPER SYSTEM. new text end
4.18 new text begin Subdivision 1. Requirement. The owner of a building shall establish a fire life safety new text end
4.19 new text begin damper and smoke control system inspection verification program to ensure that fire life new text end
4.20 new text begin safety dampers and smoke control systems are in working order to prevent the spread of new text end
4.21 new text begin fire and smoke throughout a building. new text end
4.22 new text begin Subd. 2. Required testing. (a) All owners of buildings are responsible for ensuring that new text end
4.23 new text begin newly installed fire life safety dampers are subject to fire life safety damper testing under new text end
4.24 new text begin this section or under rules adopted by the state fire marshal before use is permitted. new text end
4.25 new text begin (b) The testing of fire life safety dampers must include the visual inspection method in new text end
4.26 new text begin applicable chapters in accordance with NFPA 80, NFPA 101, and NFPA 105. new text end
4.27 new text begin (c) Once installed, a building owner must periodically inspect and test fire life safety new text end
4.28 new text begin dampers no less than once after the first year of installation, and once every four years new text end
4.29 new text begin thereafter, except for hospitals. In hospitals, the building owner must inspect and test fire new text end
4.30 new text begin life safety dampers no less than once after the first year of installation and once every six new text end
4.31 new text begin years thereafter. The periodic testing of fire life safety dampers must include the visual new text end
4.32 new text begin inspection method in accordance with NFPA 80, NFPA 101, and NFPA 105. The remote new text end
5.1 new text begin inspection method, as defined in NFPA 80, NFPA 101, and NFPA 105 must not be used in new text end
5.2 new text begin place of visual inspection for the periodic testing required under this subdivision. All fire new text end
5.3 new text begin and smoke dampers must be tested as required under this section regardless of location. new text end
5.4 new text begin Subd. 3. Required qualifications of individual testers of fire smoke dampers. (a) new text end
5.5 new text begin The state fire marshal shall establish and administer a program to review and approve new text end
5.6 new text begin third-party inspection training and certification programs to ensure conformance to the new text end
5.7 new text begin minimum qualifications under this section. new text end
5.8 new text begin (b) Inspections and tests under this section must be performed by a qualified inspector. new text end
5.9 new text begin For the purposes of this section, a "qualified inspector" means: new text end
5.10 new text begin (1) authorized state or local fire department personnel; or new text end
5.11 new text begin (2) qualified fire smoke damper inspector. new text end
5.12 new text begin Subd. 4. Required testing of smoke control systems. (a) A building owner is responsible new text end
5.13 new text begin for ensuring that smoke control systems under this section are tested for acceptance as new text end
5.14 new text begin required by the applicable NFPA standards referenced in this section or as set forth in rules new text end
5.15 new text begin adopted by the state fire marshal. new text end
5.16 new text begin (b) Once installed, the building owner must periodically inspect and test smoke control new text end
5.17 new text begin systems at the following intervals: new text end
5.18 new text begin (1) dedicated smoke control systems shall be tested at least semiannually; and new text end
5.19 new text begin (2) nondedicated smoke control systems shall be tested at least annually. new text end
5.20 new text begin (c) Testing of smoke control systems shall include tests to determine that airflow new text end
5.21 new text begin quantities and pressure differences are code compliant, including at the following locations: new text end
5.22 new text begin (1) across smoke barrier openings; new text end
5.23 new text begin (2) at the air makeup supplies; and new text end
5.24 new text begin (3) at smoke exhaust equipment. new text end
5.25 new text begin Subd. 5. Required qualifications of individual testers of smoke control systems. (a) new text end
5.26 new text begin The state fire marshal shall establish and administer a program to review and approve new text end
5.27 new text begin third-party inspection training and certification programs to ensure conformance to the new text end
5.28 new text begin minimum qualifications set forth in this section. new text end
5.29 new text begin (b) Inspections and tests under this section shall be performed by a qualified inspector. new text end
5.30 new text begin For the purposes of this section, qualified inspector means: new text end
5.31 new text begin (1) authorized state or local fire department personnel; or new text end
6.1 new text begin (2) a qualified smoke control system inspector. new text end
6.2 new text begin Subd. 6. Certificate of operation. (a) If the fire life safety dampers, smoke control new text end
6.3 new text begin systems, or HVAC duct system that contains a fire life safety damper or is part of a smoke new text end
6.4 new text begin control system pass the applicable inspections and tests, the person performing the inspection new text end
6.5 new text begin or test shall execute a certificate of operation verifying compliance with this section. The new text end
6.6 new text begin certificate of operation shall provide the following information: new text end
6.7 new text begin (1) the name and certification number of the individual conducting the inspection or new text end
6.8 new text begin test; new text end
6.9 new text begin (2) the name of the inspector's employer; new text end
6.10 new text begin (3) the name of the building owner and address of the property; new text end
6.11 new text begin (4) the location of all smoke dampers, fire dampers, combination fire/smoke dampers, new text end
6.12 new text begin and smoke control systems inspected or tested; and new text end
6.13 new text begin (5) the date of the inspection or test. new text end
6.14 new text begin (b) The building owner shall maintain a copy of the certificate of operation on the building new text end
6.15 new text begin property and make the certificate available for inspection upon request. new text end
6.16 new text begin Subd. 7. Testing failures. (a) In the event an inspection or test reveals deficiencies in new text end
6.17 new text begin fire life safety dampers or smoke control systems, the person who conducted the inspection new text end
6.18 new text begin or test shall prepare a deficiency report for the building owner identifying the nature of the new text end
6.19 new text begin deficiency and reasons for noncompliance. The deficiency report shall also contain the name new text end
6.20 new text begin and certification number of the individual conducting the inspection or test and that person's new text end
6.21 new text begin employer; the name of the building owner; address of the property; the location of all fire new text end
6.22 new text begin dampers, smoke dampers, combination fire smoke dampers, and smoke control systems new text end
6.23 new text begin inspected or tested; and the date of the inspection or test. The building owner shall take the new text end
6.24 new text begin necessary steps to ensure the defective equipment is replaced or repaired and that compliance new text end
6.25 new text begin with the applicable inspection and testing requirements have been achieved. A building new text end
6.26 new text begin owner who does not comply within 30 days is in violation of this section. new text end
6.27 new text begin (b) The building owner shall post a notice of verification of the testing and inspection new text end
6.28 new text begin of fire life safety dampers and smoke control systems in the outside lobby window of the new text end
6.29 new text begin building or other area clearly visible to the public. The verification shall state the address new text end
6.30 new text begin of the building and the date of the last fire life safety damper inspection, smoke control new text end
6.31 new text begin system inspection, and the date that each inspection expires. new text end
6.32 new text begin Subd. 8. Submissions and inspections. (a) Building owners shall submit copies of new text end
6.33 new text begin operation certificates to the state fire marshal documenting compliance with the testing new text end
7.1 new text begin requirements of this section within 30 days of obtaining certificates of operation. The state new text end
7.2 new text begin fire marshal shall commence enforcement actions for any instance of noncompliance. new text end
7.3 new text begin (b) When the state fire marshal conducts an annual fire inspection of any building, it new text end
7.4 new text begin shall inspect the building owner's fire life safety dampers, smoke control systems, and new text end
7.5 new text begin HVAC duct system that contain a fire life safety damper or is part of a smoke control system new text end
7.6 new text begin control system certificate of operation to ensure it complies with the requirements of this new text end
7.7 new text begin section and commence enforcement actions if violations are found. new text end
7.8 new text begin Subd. 9. Enforcement and penalties. The state fire marshal shall assess a $100 civil new text end
7.9 new text begin penalty for each day of noncompliance to any building owner in violation of this section. new text end
7.10 new text begin Subd. 10. Rulemaking. The commissioner of public safety shall adopt rules to carry new text end
7.11 new text begin out the provisions of this section. new text end
7.12 new text begin EFFECTIVE DATE. Subdivisions 1 to 4 are effective one year after publication in the new text end
7.13 new text begin State Register of rules adopted under subdivision 10. Subdivisions 5 to 9 are effective the new text end
7.14 new text begin day following final enactment of rules adopted under subdivision 10. Subdivision 10 is new text end
7.15 new text begin effective the day following final enactment. new text end
7.16Sec. 3. new text begin EFFECTIVE DATE. new text end
7.17 new text begin Unless otherwise provided, this act takes effect the day following enactment of new text end
7.18 new text begin administrative rules to review and approve third-party inspection training and certification new text end
7.19 new text begin programs by the state fire marshal or July 1, 2025, whichever occurs first. new text end

Bill information comes from public records published by the Office of the Revisor of Statutes, the Minnesota House and the Minnesota Senate. AI summaries are written by MinneSlate and are not official. MinneSlate is independent and is not affiliated with the State of Minnesota or the Minnesota Legislature.